Skip to main navigation Skip to search Skip to main content

Ventilation and air cleaning to limit aerosol particle concentrations in a gym during the COVID-19 pandemic

  • Bert Blocken
  • , Thijs van Druenen
  • , Alessio Ricci
  • , Luyang Kang
  • , Twan van Hooff
  • , Peng Qin
  • , Lili Xia
  • , Claudio Alanis Ruiz
  • , Dennis Arts
  • , Jan Diepens
  • , G.A. Maas
  • , Stefanie Gillmeier
  • , Steven Vos
  • , Aarnout Brombacher
  • Eindhoven Technical University, Eindhoven, Netherlands
  • KU Leuven
  • University of Genoa

Research output: Contribution to journalArticleScientificpeer-review

Abstract

SARS-CoV-2 can spread by close contact through large droplet spray and indirect contact via contaminated objects. There is mounting evidence that it can also be transmitted by inhalation of infected saliva aerosol particles. These particles are generated when breathing, talking, laughing, coughing or sneezing. It can be assumed that aerosol particle concentrations should be kept low in order to minimize the potential risk of airborne virus transmission. This paper presents measurements of aerosol particle concentrations in a gym, where saliva aerosol production is pronounced. 35 test persons performed physical exercise and aerosol particle concentrations, CO2 concentrations, air temperature and relative humidity were obtained in the room of 886 m³. A separate test was used to discriminate between human endogenous and exogenous aerosol particles. Aerosol particle removal by mechanical ventilation and mobile air cleaning units was measured. The gym test showed that ventilation with air-change rate ACH = 2.2 h−1, i.e. 4.5 times the minimum of the Dutch Building Code, was insufficient to stop the significant aerosol concentration rise over 30 min. Air cleaning alone with ACH = 1.39 h−1 had a similar effect as ventilation alone. Simplified mathematical models were engaged to provide further insight into ventilation, air cleaning and deposition. It was shown that combining the above-mentioned ventilation and air cleaning can reduce aerosol particle concentrations with 80 to 90% , depending on aerosol size. This combination of existing ventilation supplemented with air cleaning is energy efficient and can also be applied for other indoor environments.
Original languageEnglish
Article number107659
Number of pages16
JournalBuilding and Environment
Volume193
DOIs
Publication statusPublished - 15 Apr 2021

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 3 - Good Health and Well-being
    SDG 3 Good Health and Well-being
  2. SDG 7 - Affordable and Clean Energy
    SDG 7 Affordable and Clean Energy

Keywords

  • covid-19
  • aerosol
  • sports clubs
  • fitness center
  • building ventilation
  • air purifier

Fingerprint

Dive into the research topics of 'Ventilation and air cleaning to limit aerosol particle concentrations in a gym during the COVID-19 pandemic'. Together they form a unique fingerprint.

Cite this